Strany 1 - PRIMECENTER M1 19-inch Rack

User Manual - EnglishPRIMECENTER M1 19-inch RackRack System for PRIMERGY, PRIMEQUEST, BS2000, STORAGEFebruary 2012

Strany 2 - Copyright and Trademarks

10 Preface© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_work\pcr-m1-

Strany 3 - Before reading this manual

100 Power Distribution© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_

Strany 4

101Power Distribution7.3.7.3 Installation options for 600 mm wide symmetrical racksPerforming the taskÊ Install the socket strips onto the PDU kit

Strany 5 - Contents

102 Power Distribution© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_

Strany 6

103Power Distribution7.3.8.1 Installation options for 700 mm wide asymmetrical racksPerforming the taskÊ Install the PDU brackets as described on p

Strany 7

104 Power Distribution© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_

Strany 8

105Power Distribution7.4 Connecting to the potential compensating systemIf required by local regulations, the PRIMECENTER M1 19-inch rack can be co

Strany 9 - 1 Preface

106 Power Distribution© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_

Strany 10 - 1.1 Features

1078 Optional accessoriesVarious accessories are optionally available with the PRIMECENTER M1 19-inch rack, including:– Anti-tilt protection– Rack

Strany 11

108 Optional accessories© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\0

Strany 12

1099 AppendixIn this chapter you can find additional information on special tasks: – Door conversionI More information can be found at:9.1 Door con

Strany 13 - 1.2 Target Group

11PrefaceThe optimized cable management patented by Fujitsu Technology Solutions is a major highlight in the asymmetrical PRIMECENTER M1 rack syste

Strany 21

110 Appendix© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_work\pcr-m

Strany 22 - Important Information

12 Preface© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_work\pcr-m1-

Strany 23 - 3Overview

13Preface1.2 Target GroupThis manual is intended for those responsible for installing and maintaining the PRIMECENTER M1 19-inch rack (service pers

Strany 24

14 Preface© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_work\pcr-m1-

Strany 25

15Preface1.5 Notational Conventionsbold type Used for emphasis in the body of the text“quotation marks” Used for references to other chapters, sect

Strany 26

16 Preface© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_work\pcr-m1-

Strany 27 - 4 Preparations

172 Important Information 2.1 Safety Instructions I The following safety instructions are also provided in the manual "Safety Notes and Regula

Strany 28 - Preparations

18 Important Information© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\0

Strany 29

19Important InformationV CAUTION!The AC main power connection for the PRIMECENTER M1 19-inch rack must be installed by an authorized electrician ap

Strany 30

Comments… Suggestions… Corrections…The User Documentation Department would like toknow your opinion of this manual. Your feedback helpsus optimize our

Strany 31

20 Important Information© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\0

Strany 32 - 4.5 Opening the rack door

21Important InformationFujitsu Technology Solutions GmbH Recycling CenterD-33106 PaderbornTel. ++49 5251 525 - 1410Fax ++49 5251 525 - 321410

Strany 33 - 4.6.1 Inserting Cage Nuts

22 Important Information© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\0

Strany 34 - 4.6.2 Inserting Spring Nuts

233OverviewThe PRIMECENTER M1 19-inch Rack is a universal rack system for the creation of integrated data center infrastructure solutions from serv

Strany 35

24 Overview© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_work\pcr-m1

Strany 36

25Overviewinstalled components upon removal of the upper/side covers. Optimized cable management solutions for the various rack types also play the

Strany 37 - Figure 10: Height unit (HU)

26 Overview© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_work\pcr-m1

Strany 38 - 5.1 Support Systems

274 PreparationsThis chapter describes the preparations for installation and all the tasks involved in setting up and operating the PRIMECENTER M1

Strany 39

28 Preparations© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_work\pc

Strany 40

29Unpacking and checking the delivery unit4.1 Unpacking the delivery unitI For a description to unpack the PRIMECENTER M1 19-inch rack please refer

Strany 41

Before reading this manualFor your safetyThis manual contains important information for safely and correctly using this product.Carefully read the

Strany 42

30 Setting up the PRIMECENTER Rack© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\Use

Strany 43

31Setting up the PRIMECENTER RackFigure 5: Adjusting the PRIMECENTER M1 19-inch rackÊ Adjust the rack on all three axes (X,Y,Z) with the leveling f

Strany 44

32 Setting up the PRIMECENTER Rack© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\Use

Strany 45 - Cable Inlets and Outlets

33Inserting mounting elements4.6 Inserting mounting elements4.6.1 Inserting Cage NutsIntroductionCage nuts are placed into the support uprights. A

Strany 46

34 Inserting mounting elements© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Ma

Strany 47

355 Preparing to install rack componentsThis chapter describes how to prepare the PRIMECENTER M1 19-inch rack to install rack components. Refer to

Strany 48

36 Preparing to install rack components© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manual

Strany 49

37Preparing to install rack componentsThe Height Unit (HU)The unit of measurement used in the PRIMECENTER M1 19-inch rack is the height unit (HU).

Strany 50

38 Support systems© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_work

Strany 51

39Mounting in the front 19-inch area5.2.1 Mounting support bracketsI Support brackets are required only for asymmetrical PRIMECENTER M1 19-inch rac

Strany 52

© cognitas. Gesellschft für Technik-Dokumentation mbH 2012 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_work\pcr-m1-rack-um-en

Strany 53 - 6 Cable Management

40 Mounting in the front 19-inch area© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\

Strany 54

41Mounting in the rear 19-inch area5.3 Mounting in the rear 19-inch areaYou can mount additional rack components in the rear 19-inch area if:– the

Strany 55

42 Mounting in the expansion area© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User

Strany 56

43Mounting in the expansion area5.4.1 Mounting Rack ComponentsFigure 14: Mounting a rack component in the expansion areaÊ Remove the cover (3) from

Strany 57 - 6.2.2 Disconnecting Cables

44 Cable Inlets and Outlets© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manua

Strany 58 - 6.3 Routing Cables

45Cable Inlets and OutletsThe following figure shows the cable cut-outs in the bottom area in 600 mm racks:Figure 16: Cable cut-outs for cable rout

Strany 59

46 Cable Inlets and Outlets© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manua

Strany 60 - Performing the task

47Cable Inlets and OutletsFigure 18: Cable cut-out with edge protectorsÊ Mount the edge protectors to the cut-out (see following figure).I Make sur

Strany 61

48 Cable Inlets and Outlets© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manua

Strany 62

49Cable Inlets and Outlets5.5.2 Cable routing through the top coverThe 42 HU racks offer the possibility to route cables through the top cover by m

Strany 63

Contents1 Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.1 Features . . . . . . . .

Strany 64 - V Caution!

50 Cable Inlets and Outlets© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manua

Strany 65

51Cable Inlets and OutletsFigure 23: Mounting the edge protectorÊ Mount the edge protector around the top cover cut-out to prevend cable damaging b

Strany 66

52 Cable Inlets and Outlets© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manua

Strany 67 - 7 Power Distribution

536 Cable ManagementThe cable management comprises the following parts:– lateral cable management (only for asymmetrical 700 mm PRIMECENTER M1 19-i

Strany 68

54 Mounting the Cable Management© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User

Strany 69 - 7.1 Installing PDU brackets

55Mounting the Cable Management6.1.2 Cable guide with cable clipsI The cable guide with cable clips can only be used in asymmetrical 700 mm PRIMECE

Strany 70

56 Connecting and Disconnecting Cables© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals

Strany 71

57Connecting and Disconnecting CablesMake sure that the cabling of devices with a "dual power feed" fulfils the conditions of the high av

Strany 72

58 Connecting and Disconnecting Cables© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals

Strany 73

59Connecting and Disconnecting Cables6.3.1 Routing cables in the rackThe following photo shows as a sample how to route cables in the rack:Figure 2

Strany 74

Contents© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_work\pcr-m1-ra

Strany 75

60 Connecting and Disconnecting Cables© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals

Strany 76

61Connecting and Disconnecting Cables6.3.3 Cable routing and strain relief for the built-in rack components in asymmetrical racksThe rack component

Strany 77

62 Connecting and Disconnecting Cables© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals

Strany 78

63Connecting and Disconnecting CablesFigure 32: Rack top view: rack component pulled out fully105% front of the Rackconnectorslateral cable managem

Strany 79

64 Connecting and Disconnecting Cables© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals

Strany 80

65Connecting and Disconnecting Cables6.3.5 Direct ConnectionThe example below shows how to connect cables directly to a rack component installed on

Strany 81

66 Connecting and Disconnecting Cables© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals

Strany 82

677 Power DistributionThe PRIMECENTER M1 19-inch rack offers various possibilities for distributing power to the integrated rack components. Theref

Strany 83 - Power Distribution

68 Power Distribution© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_w

Strany 84

69Power Distribution7.1 Installing PDU bracketsIntroductionAll PDUs have to be mounted using versatile mounting brackets (PDU brackets). These PDU

Strany 85

Contents7.3.7 Socket strip extension 3 safety plugs and assembly . . . . . . . 987.3.8 Single-phase 4+1-way socket strip and assembly . .

Strany 86

70 Power Distribution© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_w

Strany 87

71Power Distribution7.2 Mounting socket strips onto PDU kit 3HUI Horizontal mounting is the only way to mount socket strips into a 600 mm rack.Figu

Strany 88

72 Power Distribution© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_w

Strany 89

73Power Distribution7.3 Installing the socket strips7.3.1 32 A single-phase 5-way socket strip IntroductionI For more information, see the configur

Strany 90

74 Power Distribution© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_w

Strany 91

75Power Distribution7.3.1.2 Installation options for 700 mm wide symmetrical racksPerforming the taskÊ Install the PDU brackets as described on pag

Strany 92

76 Power Distribution© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_w

Strany 93

77Power Distribution7.3.2 Single-phase 10-way socket strip w/o plugIntroductionI For more information, see the configurator: https://partners.ts.fu

Strany 94

78 Power Distribution© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_w

Strany 95

79Power Distribution7.3.2.2 Installation options for 700 mm wide symmetrical racksPerforming the taskÊ Install the PDU brackets as described on pag

Strany 96

Contents© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_work\pcr-m1-ra

Strany 97

80 Power Distribution© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_w

Strany 98

81Power Distribution7.3.3 32 A three-phase 15-way socket stripIntroductionI For more information, see the configurator: https://partners.ts.fujitsu

Strany 99

82 Power Distribution© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_w

Strany 100

83Power Distribution7.3.3.2 Installation options for 700 mm wide symmetrical racksPerforming the taskÊ Install two PDU brackets as described on pag

Strany 101

84 Power Distribution© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_w

Strany 102

85Power Distribution7.3.4 Three-phase 24-way socket strip IntroductionI For more information, see the configurator: https://partners.ts.fujitsu.com

Strany 103

86 Power Distribution© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_w

Strany 104

87Power Distribution7.3.4.2 Installation options for 700 mm wide symmetrical racksPerforming the taskÊ Install two PDU brackets as described on pag

Strany 105 - Figure 73: Grounding screw

88 Power Distribution© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_w

Strany 106 - 7.5 Power Supply via UPS

89Power Distribution7.3.5 Single-phase 8-way socket strip and assemblyIntroductionI For more information, see the configurator: https://partners.ts

Strany 107 - 8 Optional accessories

91 PrefaceThe data centers of today and tomorrow have to meet the continuously increasing requirements and demands of operators. Fujitsu has been o

Strany 108 - Optional accessories

90 Power Distribution© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_w

Strany 109 - 9 Appendix

91Power Distribution7.3.5.2 Installation options for 700 mm wide symmetrical racksPerforming the taskÊ Install two PDU brackets as described on pag

Strany 110

92 Power Distribution© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_w

Strany 111

93Power Distribution7.3.6 Single-phase 10-way socket strip and assemblyIntroductionI For more information, see the configurator: https://partners.t

Strany 112

94 Power Distribution© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_w

Strany 113

95Power Distribution7.3.6.1 Installation options for 700 mm wide asymmetrical racksPerforming the taskÊ Install the PDU brackets as described on pa

Strany 114

96 Power Distribution© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_w

Strany 115

97Power Distribution7.3.6.3 Installation options for 600 mm wide symmetrical racksPerforming the taskÊ Install the socket strips onto the PDU kit 3

Strany 116

98 Power Distribution© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_w

Strany 117 - Appendix

99Power Distribution7.3.7.1 Installation options for 700 mm wide asymmetrical racksPerforming the taskÊ Install the PDU brackets as described on pa

Komentáře k této Příručce

Žádné komentáře